- [RCBO] Residual Current Circuit Breaker with Overcurrent protection
- RCBO HSM1-2A type A 10kA 1P+N
- RCBO HSM1-4A type A 10kA 3P+N
- RCBO HSM2-2A type A 6kA 1P+N
- RCBO HSM2-4A type A 6kA 3P+N
- RCBO HSM2X-4A type A 6kA 3P+N
- RCBO HSM2-2B type B 6kA 1P+N
- RCBO HSM2-4B type B 6kA 3P+N
- [RCCB] Redisual Current Circuit Breaker
- RCCB HSL1-2A type A 10kA 1P+N
- RCCB HSL1-4A type A 10kA 3P+N
- RCCB HSL2-2A type A 6kA 1P+N
- RCCB HSL2-4A type A 6kA 3P+N
- RCCB HSL2-2B type B 6kA 1P+N
- RCCB HSL2-4B type B 6kA 3P+N
- RCCB HSL2-2EV type EV 6kA 1P+N
- RCCB HSL2-4EV type EV 6kA 3P+N
- TR Al/Cu Universal Terminal Block
- 16mm2 Al/Cu universal terminal block
- 35mm2 Al/Cu universal terminal block
- 50mm2 Al/Cu universal terminal block
- 95mm2 Al/Cu universal terminal block
- 150mm2 Al/Cu universal terminal block
- 240mm2 Al/Cu universal terminal block
- Terminal shroud for TR series Al/Cu universal terminal block
RCBO HSM2-4B type B 6kA
-
Share:
The HSM2 series 6kA type B 1P+N & 3P+N RCBOs (residual current-breaker with overload protection). It’s main use is in EV-, PV- and battery solutions (equipment without the 6mA declarations). The RCBO comes in 1p+n, 45mm width (2,5 modules) and in 3p+n, 81mm width (4,5 modules) and this in combination with a high breaking capacity of 6kA. The series ensures the best possible safety for people and equipment.
Description
HSM2 series type B RCBO compliant to product standard IEC/EN 61009-1,IEC/EN 61009-2-1, IEC/EN 62423 and with the following main technical features:
• Breaking capacity
6,000 kA |
• Electromagnetic (IEC/EN 61009-1, IEC/EN 61009-2-1;
• Type B;
• Sensitivity
30 | 100mA |
• Tripping characteristics
B | C |
• Rated current
6 | 10 | 13 | 16 | 20 | 25 | 32 | 40A |
Application benefits:
• Supply possible both from top and bottom;
• Fork type busbar connection (above and below) up to 16mm² and cable connection up to 25mm² cables;
• Easy troubleshooting and reduced downtime for maintenance operations thanks to the earth fault indicator (blue/red flag on the window);
Technical
Type | HSM2-2B | HSM2-4B | |||
Standards | IEC/EN 61009-1, IEC/EN 61009-2-1, IEC/EN 62423; | ||||
Certificate | KEMA KEUR, CB, CE, UKCA, RoHS | ||||
Country of origin | CHINA | ||||
Electrical features |
Type (wave form of the earth leakage sensed) | Type B | |||
Number of poles | 1P+N | 3P+N | |||
Rated current | In | A | 6, 10, 16, 20, 25, 32, 40 A | ||
Rated sensitivity | IΔn | mA | 30, 100, 300 mA | ||
Rated voltage | Ue | V | 220/230/240 V | 380/400/415 V | |
Operating time | Type A / Type AC | Instantaneous | |||
Insulation voltage | Ui | V | 500V AC | ||
Overvoltage category | III | ||||
Pollution degree | 2 | ||||
Operating voltage of circuit test | V | 187 - 264 V | 230 - 485 V | ||
Rated frequency | Hz | 50/60 Hz | |||
Rated breaking capacity acc. to IEC/EN 61009-1 | Icn | A | 6,000 A | ||
Rated breaking capacity acc. to IEC/EN 60947-2 (Only referring to short circuit test) |
Icu | A | 10,000 A | ||
Ics | A | 5,000 A (50%Icu) | |||
Rated residual breaking capacity acc.to IEC/EN 61009-1 |
IΔm | A | 3,000 A | ||
Rated impulse withstand voltage (1.2/50) | Uimp | kV | 4 kV | ||
Dielectric test voltage at ind. freq. for 1 min. | kV | 2.5 kV (50/60Hz, 1 min.) | |||
Thermomagnetic release – characteristics | Characteristics B: 3In - 5In | ||||
Characteristics C: 5In - 10In | |||||
Energy limiting class acc. to EN 61009-1 | 3 | ||||
Surge current resistance (wave 8/20) | A | 3,000 A | |||
Mechanical features |
Housing | Insulation group I - II, RAL 7035 | |||
Toggle | Insulation group II, RAL 5017 | ||||
Test button | Insulation group II, RAL 2000 | ||||
Contact position indication | Green / Red window | ||||
Electrical life | Operations | 4,000 cycles | |||
Mechanical life | Operations | 10,000 cycles | |||
Protection degree acc. to EN 60529 | Housing | IP4X | |||
Terminals | IP2X | ||||
Shock resistance acc. to IEC/EN 60068-2-27 | 25g - 2 shocks - 13ms | ||||
Vibration resistance acc. to IEC/EN 60068-2-6 | 0.1 mm or 1 g - 20 cycles at 5…150…5 Hz | ||||
Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30 | °C/RH | 28 cycles with 55°C/90-96% and 25°C/95-100% | |||
Reference temperature for setting of thermal element | °C | 30 °C | |||
Ambient temperature (with daily average ≤ +35 °C) | °C | -25… +40 °C | |||
Storage temperature | °C | -40… +70 °C | |||
* IEC/EN 60947-2 certificate and test-report are not available at present, the use of these values is the responsibility of the user | |||||
Installation |
Terminal type | Twin-purpose terminal (lift / open-mouthed) | |||
Terminal size for cables | bottom / top | mm² | 25/35 mm² | ||
Terminal size for PIN busbar | bottom / top | mm² | 10/16 mm² | ||
Terminal size for FORK busbar | bottom / top | mm² | M6 - 10/16 mm² | ||
Solid /stranded wiring |
1x 1mm² - 35mm² 2 x 1mm² - 16mm² * |
||||
Flexible wires with or without ferrules |
1x 1mm² - 25mm² 2 x 1mm² - 10mm² * |
||||
Tightening torque | bottom / top | 2 Nm | |||
Stripping length of the cable | 10 mm | ||||
Mounting |
On DIN rail EN 60715 (35mm) by means of mounting clip |
||||
Mounting position | Any | ||||
Connect from | Top/bottom terminals | ||||
Dimensions (H x W x D) | mm | 89 x 45 x 72 mm | 89 x 81 x 72 mm | ||
Weight | kg | 0.22 kg | 0.43 kg | ||
Package |
Packing A (Individual box) |
Quantity | pieces | 1 | 1 |
Dimension (H*W*D) | mm | 90*50*80 mm | 92*88*80 mm | ||
Weight | kg | 0.23 kg | 0.44 kg | ||
Packing B (*A) (Middle box) |
Quantity | pieces | 4 | 2 | |
Dimension (H*W*D) | mm | 215*100*88 mm | 182*100*88 mm | ||
Weight | kg | 1.38 kg | 1.33 kg | ||
Packing C (*B) (Master carton) |
Quantity | pieces | 40 | 20 | |
Dimension (H*W*D) | mm | 505*225*195 mm | 505*195*195 mm | ||
Weight | kg | 10 kg | 10 kg | ||
Combination with auxiliary elements |
Auxiliary contact | NA (yes) | NA (yes) | ||
Allarm contact | NA (yes) | NA (yes) | |||
Shunt trip | NA (yes) | NA (yes) | |||
Auxiliary contact for bottom fitting | NA (yes) | NA (yes) | |||
Undervoltage release | NA (yes) | NA (yes) | |||
Overvoltage release | NA (yes) | NA (yes) | |||
Motor operating device | NA (yes) | NA (yes) |